At a glance

Typical zonesZone 1 · 2underground tank interior Zone 0
Gas groupIIApetrol, diesel and LPG
Temperature classT3 or betterpetrol vapour needs T3
ProtectionEx d · Ex eGb level, IP66

Which area is which zone?

The table below shows the typical classification seen in this industry; the exact boundaries depend on ventilation, release sources and the ground layout and are set in your site's explosion protection document. For the zone concepts in detail, see our article on Zone 0, 1, 2 and 20, 21, 22.

AreaTypical zoneNote
Underground tank interiorZone 0The vapour space is a continuous explosive atmosphere.
Tank fill points and vent pipe outletsZone 1Zone 2Zone 1 close to the opening, Zone 2 around it.
Fuel dispenserZone 1Zone 2The housing interior is usually Zone 1; the surroundings and the area near the ground are usually Zone 2.
Tank manholes, pump pitsZone 1Heavier-than-air vapour collects below ground level.
LPG filling point and tank valvesZone 1Zone 2Zone 1 around the filling coupling and relief valve, Zone 2 beyond.
Inside the tank farm bundZone 2Risk of overfill and leaks; low points can be Zone 1.
Tanker loading / unloading gantryZone 1Zone 2Zone 1 around the loading arm and the tanker hatch.
Shop, office buildingSafe areaUsually outside the hazardous area when separated by distance and walls.
Zone 0 continuousZone 1 occasionalZone 2 rare, short periods

Gases on site and the classes they need

PetrolIIAT3
Propane (LPG)IIAT2
Butane (LPG)IIAT2
Ethanol (bioethanol)IIAT2
Methane (CNG)IIAT1

Rule of thumb: petrol, diesel and LPG are in group IIA; the deciding factor is usually the low ignition temperature of petrol, so choose T3 or better. LPG and petrol vapour are heavier than air: low points such as pits, trenches and manholes are classified more strictly than their surroundings.

Product groups for this industry

Frequently used in this industry

What to check when selecting

  • The equipment category must suit the zone: at least 2 G (Gb) for Zone 1, 3 G (Gc) for Zone 2 and only 1 G (Ga) inside the tank (e.g. level sensors).
  • Wherever petrol is present the temperature class must be T3 or better; T2 is enough where only LPG is present, but T3 leaves room if petrol is added later.
  • For luminaires on canopies and loading gantries choose IP66 and UV-resistant housings to withstand rain and washing.
  • For buried armoured cable use a certified gland that terminates the armour and suits the enclosure's protection type; a certified blanking plug in every unused entry.
  • Equipment in pump pits and manholes needs a suitable IP rating against flooding, and cable ducts must be sealed against vapour migration.

Frequently asked questions

Is ex-proof equipment also needed for a diesel pump?

Diesel has a high flash point and on its own usually creates a smaller hazardous area. At stations, however, diesel and petrol usually share the same island and dispenser, so the classification follows petrol.

Is IIA equipment enough for LPG?

Propane and butane are in group IIA; equipment marked IIA, IIB or IIC can be used. If petrol is present in the same area, T3 applies for the temperature class.

Who classifies the zones?

The employer has an explosion protection document prepared under the ATEX workplace rules (Directive 1999/92/EC, in Türkiye the related regulation); the zone boundaries are set out in that document.