At a glance

Typical zonesZone 1 · 2mixer and tank interiors Zone 0
Gas groupIIA · IIBmost solvents are IIA
Temperature classT3 or betterhexane needs T3
ProtectionEx d · Ex eGb level, IP65 or higher

Which area is which zone?

The table below shows the typical classification seen in this industry; the exact boundaries depend on the solvents used, ventilation and open-container work and are set in your site's explosion protection document. For the zone concepts in detail, see our article on Zone 0, 1, 2 and 20, 21, 22.

AreaTypical zoneNote
Mixer and mixing tank interiorZone 0Solvent vapour is always present; usually Zone 0 in open-top tanks.
Mixing / dispersion roomZone 1Zone 2Open containers, pouring and cleaning; Zone 1 or 2 depending on ventilation.
Spray booth interior and exhaust ductZone 1Vapour and mist form during spraying; usually Zone 1.
Around spray booth openingsZone 2Around doors and workpiece entry and exit openings.
Filling and packaging lineZone 1Zone 2Zone 1 around the filling nozzle, Zone 2 along the rest of the line.
Solvent store (tanks and drums)Zone 1Zone 2Storage in closed drums is usually Zone 2; transfer points are Zone 1.
Drying oven interiorZone 1Zone 2Evaporating solvent is diluted by ventilation; Zone 1 or 2 depending on the design.
Office, compressor roomSafe areaKept outside the hazardous area by distance and separate ventilation.
Zone 0 continuousZone 1 occasionalZone 2 rare, short periods

Gases on site and the classes they need

TolueneIIAT1
XyleneIIAT1
AcetoneIIAT1
EthanolIIAT2
IsopropanolIIAT2
n-HexaneIIAT3

Rule of thumb: most solvents used in paints and varnishes are in group IIA, but recipes change, so choosing IIB leaves a margin. For the temperature class, solvents with a low ignition temperature such as hexane decide: choose T3 or better. Near drying ovens, also check the equipment's ambient temperature limit.

Product groups for this industry

Frequently used in this industry

What to check when selecting

  • The equipment category must suit the zone: at least 2 G (Gb) for Zone 1, 3 G (Gc) for Zone 2 and only 1 G (Ga) inside a mixing tank.
  • Choose the temperature class from the ignition temperatures in the safety data sheets of all solvents you use; update the list when recipes change.
  • Paint mist builds up on luminaires inside spray booths: choose easy-to-clean housings rated IP65 or higher and clean the glass regularly; deposits hinder heat dissipation.
  • Powder coating booths can also create a dust zone (21 / 22) besides the gas zone; check the equipment's dust marking (e.g. Ex tb IIIC) as well.
  • Equipment near drying ovens must not exceed the upper limit of its certified ambient range (e.g. +40 °C or +60 °C).

Frequently asked questions

Can ordinary (non-ex-proof) luminaires be used in a solvent store?

Not if the store is classified as Zone 1 or Zone 2; certified equipment of a suitable category is needed. Keeping drums closed does not by itself change the classification; it is assessed together with ventilation and release sources.

Which type of luminaire is preferred in a spray booth?

Usually Zone 1 (Gb) certified linear LED luminaires are used, mounted behind glass in the booth ceiling or walls, or directly inside the booth. The booth manufacturer's instructions and the explosion protection document both apply.

Who classifies the zones?

The employer has an explosion protection document prepared under the ATEX workplace rules (Directive 1999/92/EC, in Türkiye the related regulation); the zone boundaries are set out in that document.

Sources

Let us prepare a product list for your production area

Share the zones, the solvents you use and the cable entries; we will send a quotation including luminaires, boxes, glands and blanking plugs.

Request a quote →

This article is general information; your site's explosion protection document and the product certificate are decisive when selecting equipment.