At a glance
Which area is which zone?
The table below shows the typical classification seen in this industry; the exact boundaries depend on the solvents used, ventilation and open-container work and are set in your site's explosion protection document. For the zone concepts in detail, see our article on Zone 0, 1, 2 and 20, 21, 22.
| Area | Typical zone | Note |
|---|---|---|
| Mixer and mixing tank interior | Zone 0 | Solvent vapour is always present; usually Zone 0 in open-top tanks. |
| Mixing / dispersion room | Zone 1Zone 2 | Open containers, pouring and cleaning; Zone 1 or 2 depending on ventilation. |
| Spray booth interior and exhaust duct | Zone 1 | Vapour and mist form during spraying; usually Zone 1. |
| Around spray booth openings | Zone 2 | Around doors and workpiece entry and exit openings. |
| Filling and packaging line | Zone 1Zone 2 | Zone 1 around the filling nozzle, Zone 2 along the rest of the line. |
| Solvent store (tanks and drums) | Zone 1Zone 2 | Storage in closed drums is usually Zone 2; transfer points are Zone 1. |
| Drying oven interior | Zone 1Zone 2 | Evaporating solvent is diluted by ventilation; Zone 1 or 2 depending on the design. |
| Office, compressor room | Safe area | Kept outside the hazardous area by distance and separate ventilation. |
Gases on site and the classes they need
Rule of thumb: most solvents used in paints and varnishes are in group IIA, but recipes change, so choosing IIB leaves a margin. For the temperature class, solvents with a low ignition temperature such as hexane decide: choose T3 or better. Near drying ovens, also check the equipment's ambient temperature limit.
Product groups for this industry
The links open each category with the Zone 1 + IIB filter; you can change the filter to suit your site.
Lighting
Linear LED and ceiling luminaires for mixing rooms, spray booths and solvent stores.
Zone 1IIB30 productsView products →Control stations
Start-stop and emergency stop stations for mixers, dissolvers and booth fans.
Zone 1IIB12 productsView products →Junction and distribution boxes
Ex d and Ex e terminal boxes for motor, weighing and sensor cables.
Zone 1IIB17 productsView products →Cable glands
Unarmoured / armoured glands and blanking plugs for Ex d and Ex e entries.
Zone 1IIB7 productsView products →Conduit fittings
Sealing fittings, elbows, nipples and reducers for conduit systems.
Zone 1IIB12 productsView products →Plugs and sockets
Interlocked plug and socket sets for portable mixers, pumps and cleaning equipment.
Zone 1IIB7 productsView products →Frequently used in this industry
What to check when selecting
- The equipment category must suit the zone: at least 2 G (Gb) for Zone 1, 3 G (Gc) for Zone 2 and only 1 G (Ga) inside a mixing tank.
- Choose the temperature class from the ignition temperatures in the safety data sheets of all solvents you use; update the list when recipes change.
- Paint mist builds up on luminaires inside spray booths: choose easy-to-clean housings rated IP65 or higher and clean the glass regularly; deposits hinder heat dissipation.
- Powder coating booths can also create a dust zone (21 / 22) besides the gas zone; check the equipment's dust marking (e.g. Ex tb IIIC) as well.
- Equipment near drying ovens must not exceed the upper limit of its certified ambient range (e.g. +40 °C or +60 °C).
Frequently asked questions
Can ordinary (non-ex-proof) luminaires be used in a solvent store?
Not if the store is classified as Zone 1 or Zone 2; certified equipment of a suitable category is needed. Keeping drums closed does not by itself change the classification; it is assessed together with ventilation and release sources.
Which type of luminaire is preferred in a spray booth?
Usually Zone 1 (Gb) certified linear LED luminaires are used, mounted behind glass in the booth ceiling or walls, or directly inside the booth. The booth manufacturer's instructions and the explosion protection document both apply.
Who classifies the zones?
The employer has an explosion protection document prepared under the ATEX workplace rules (Directive 1999/92/EC, in Türkiye the related regulation); the zone boundaries are set out in that document.
Sources
- Çalışanların Patlayıcı Ortamların Tehlikelerinden Korunması Hakkında Yönetmelik, Official Gazette 30.04.2013, No. 28633 (in Turkish)
- Directive 1999/92/EC, Annex I: Classification of places where explosive atmospheres may occur (legislation.gov.uk)
- Ministry of Labour and Social Security of Turkey, Implementation Guide on the Protection of Workers from the Hazards of Explosive Atmospheres (in Turkish)
- IEC 60079-10-1:2020, Classification of areas, Explosive gas atmospheres (IEC Webstore)
- HSE, Hazardous Area Classification and Control of Ignition Sources
Share the zones, the solvents you use and the cable entries; we will send a quotation including luminaires, boxes, glands and blanking plugs.
This article is general information; your site's explosion protection document and the product certificate are decisive when selecting equipment.